1 Missing GFCI Protection in Required Locations

This is the single most common violation on residential inspections. The NEC requires GFCI protection in bathrooms, kitchens (countertop receptacles), garages, outdoors, unfinished basements, crawl spaces, laundry areas, and within 6 feet of sinks. The 2023 NEC expanded this further to include 250V circuits in many of these locations.

Horizontal bar chart showing the ten most commonly cited electrical code violations ordered by how often inspectors write them up
The same ten items account for the large majority of write-ups.
NEC 210.8(A) — Dwelling unit GFCI requirements by location.

How to avoid it: Know the GFCI location requirements for your adopted code edition. When in doubt, add GFCI protection — it's cheaper than a callback.

2 Overcrowded Electrical Boxes (Box Fill Violations)

Stuffing too many conductors, devices, and clamps into a box is extremely common, especially in remodel work. Each conductor, device, and fitting takes up a specific volume in cubic inches, and the box must be large enough to contain everything per NEC Article 314.16.

NEC 314.16 — Number of conductors and box fill calculations.

How to avoid it: Count every conductor, clamp, device yoke, and grounding conductor. Use a box fill calculator to verify before you close it up.

3 Improper or Missing Bonding

Bonding jumpers get missed or installed incorrectly more than most electricians want to admit. Common issues include missing bonding at water heaters, metal piping systems, gas lines, and between the grounding electrode system and the service equipment. Loose or undersized bonding jumpers are also flagged frequently.

CATCH THESE BEFORE THE INSPECTOR DOES

Photograph a rough-in and SparkCheck flags likely issues with severity and a suggested fix.

NEC 250.104 — Bonding of piping systems and exposed structural metal.

How to avoid it: Treat bonding as its own checklist item on every job. Verify the bonding jumper size using NEC Table 250.66 or 250.122 depending on the application.

4 Missing or Incorrect Arc-Fault Protection (AFCI)

AFCI protection is required in most living areas of dwelling units — bedrooms, living rooms, dining rooms, kitchens, hallways, closets, and similar rooms. Electricians sometimes miss required locations or install standard breakers instead of combination AFCI breakers.

NEC 210.12(A) — AFCI protection requirements in dwelling units.

How to avoid it: Default to AFCI breakers for every 15A and 20A, 120V branch circuit in dwelling unit living areas. It's easier to protect everything than to figure out exceptions.

5 Exposed or Unprotected Romex (NM Cable)

NM cable must be protected from physical damage. Running Romex exposed across garage walls below 8 feet, through areas subject to physical damage, or without proper stapling and support are all common violations.

NEC 334.15 and 334.23 — NM cable protection and support requirements.

How to avoid it: Protect NM cable with conduit or guard strips in areas subject to damage. Support NM cable within 12 inches of every box and at intervals not exceeding 4.5 feet.

6 Wrong Wire Size for the Circuit

Using 14 AWG on a 20A circuit, undersizing feeders, or failing to derate conductors when there are too many in a raceway — conductor sizing errors can be both a code violation and a safety hazard. This is especially common when homeowners or handymen do their own work.

NEC 240.4 — Protection of conductors and overcurrent device sizing.

How to avoid it: Always verify ampacity from NEC Table 310.16 and apply derating factors per 310.15 when required. Match the conductor to the breaker, not the other way around.

7 Missing Tamper-Resistant Receptacles

Since the 2008 NEC, tamper-resistant receptacles have been required in dwelling units. This is one of the easiest violations to catch — and one of the easiest to avoid — yet it still shows up on inspections, particularly on DIY or handyman work and sometimes on new construction where standard receptacles get mixed in.

NEC 406.12 — Tamper-resistant receptacles required in dwelling units.

How to avoid it: Use TR-rated receptacles exclusively in dwelling units. They cost pennies more than standard receptacles.

8 Improper Grounding Electrode System

Missing ground rods, disconnected water pipe bonds, or improperly connected grounding electrode conductors are common, especially in older home rewires and service upgrades. The grounding electrode system requires all present electrodes to be bonded together.

NEC 250.50 — Grounding electrode system requirements.

How to avoid it: Bond all available electrodes: metal water pipe (within 5 feet of entry), ground rods, concrete-encased electrode (Ufer ground), and building steel if present. Use the correct GEC size from NEC Table 250.66.

9 Missing Working Space Clearances

NEC 110.26 requires specific working space clearances in front of electrical equipment — typically 36 inches deep, 30 inches wide, and clear to the ceiling or 6.5 feet high. Panels installed in tight closets, behind stored items, or in locations that don't meet depth requirements get flagged regularly.

NEC 110.26 — Spaces about electrical equipment (600V or less).

How to avoid it: Measure the working space before you mount the panel. Communicate clearance requirements to the GC and homeowner so they don't stack stuff in front of it later.

10 Missing or Incorrect Circuit Directory

Every panelboard must have a legible circuit directory that identifies the purpose or use of each circuit. Handwritten, faded, or incorrect directories are a violation and a safety hazard for anyone working on the panel later — including you on a callback.

NEC 408.4 — Circuit identification requirements for panelboards.

How to avoid it: Print a clean, typed circuit directory for every panel you install or work on. Take the extra 10 minutes — it's professional and it's required.

The Bottom Line

Every one of these violations is avoidable with attention to detail and knowledge of the code. Most of them come down to rushing, cutting corners, or simply not checking. Build a personal inspection checklist that covers these 10 items and run through it before you call for inspection. It'll save you callbacks, failed inspections, and headaches.

SCAN YOUR WORK BEFORE THE INSPECTOR DOES

SparkCheck analyzes photos of your installations and flags potential code issues before inspection day.

// Free Download

GET THE FIELD PACK

Two printables: the 22-point rough-in checklist, and branded panel schedules in 24, 30 and 42 circuit that print at 4 by 5 inches and slide straight into a panel sleeve. Enter your email and the downloads open right away.

Your address comes straight to Jason. No list rental, no spam, unsubscribe any time.

Frequently asked questions

What is the single most common electrical inspection failure?
Missing or incorrectly located GFCI protection. It leads the list on nearly every inspector's tally, largely because the required locations have expanded in every recent code cycle and people are still working from the rules they learned years ago.
What happens if I fail a rough-in inspection?
You correct the cited items and call for a re-inspection. Many jurisdictions charge a re-inspection fee, and the real cost is usually the schedule hit: drywall waits, the GC's other trades wait, and you eat a return trip.
Can I use the 2023 rules if my jurisdiction is on 2020?
You can generally exceed the adopted code, and installing to a newer, stricter requirement is usually acceptable. What you cannot do is rely on a newer edition's relaxation of a rule your AHJ has not adopted. When the editions differ in a way that helps you, the adopted edition governs.
How do I keep up with which rules changed?
Read the change summaries each cycle rather than the whole book. Our 2023 breakdown and 2026 breakdown cover the changes that actually affect field work.

Keep reading

Field Tips

Rough-In Inspection Checklist: 22 Things to Check Before You Call

Read it →
Calculators

Box Fill: How to Size a Box Correctly Under NEC 314.16

Read it →
NEC Updates

GFCI vs AFCI: What Each Does and Where Each Is Required

Read it →
Field Tips

Wire and Bolt Torque: What NEC 110.14(D) Actually Requires

Read it →
// DisclaimerThe National Electrical Code® (NEC®) and NFPA 70® are registered trademarks and copyrighted publications of the National Fire Protection Association (NFPA). This article is an independent educational resource and is not affiliated with, endorsed by, or sponsored by the NFPA. All code references in this article are paraphrased for educational purposes only and do not reproduce the official text of any NEC edition. This content is not a substitute for the official NFPA 70 publication. Electricians, contractors, and students are encouraged to purchase the official National Electrical Code from the NFPA at nfpa.org for complete and authoritative code text. Always verify requirements with the code edition adopted by your jurisdiction and your Authority Having Jurisdiction (AHJ).