What Is Voltage Drop and Why Does It Matter?

Voltage drop is the reduction in voltage as electrical current flows through a conductor. Every wire has resistance, and the longer the wire and the more current it carries, the more voltage is lost between the source and the load. The result: equipment at the end of the run doesn't get the voltage it needs to operate properly.

The NEC addresses voltage drop in informational notes rather than mandatory requirements, but inspectors and engineers treat the recommendations seriously. Poor voltage drop means flickering lights, overheating motors, tripped breakers, and unhappy customers.

NEC 210.19(A) Informational Note No. 4 — Recommends that branch circuit voltage drop not exceed 3%, and that the total voltage drop for both feeder and branch circuit not exceed 5%.

The Voltage Drop Formula

For single-phase circuits, the standard voltage drop formula is:

VD = (2 × K × I × D) / CM
Single-Phase Voltage Drop Formula

Where:

The "2" in the formula accounts for the round-trip distance — current flows out on the hot conductor and returns on the neutral.

For three-phase circuits, replace the 2 with 1.732 (the square root of 3):

VD = (1.732 × K × I × D) / CM
Three-Phase Voltage Drop Formula

Step-by-Step: How to Calculate

Step 1: Gather Your Values

You need four pieces of information: the conductor material (copper or aluminum), the load current in amps, the one-way distance from the panel to the load in feet, and the wire size you're planning to use (which gives you the circular mil area).

Step 2: Look Up Circular Mils

Common circular mil values for copper conductors:

Step 3: Plug In and Calculate

Example 1 — Residential Branch Circuit

Scenario: 20A load on #12 AWG copper, 150-foot run, 120V single-phase.

VD = (2 × 12.9 × 20 × 150) / 6,530

VD = 77,400 / 6,530 = 11.85 volts

Percentage: 11.85 / 120 = 9.9% — This exceeds the 3% recommendation significantly. You need to upsize the conductor.

With #8 AWG: (2 × 12.9 × 20 × 150) / 16,510 = 4.69V (3.9%) — Still over 3%. Consider #6 AWG or reducing the circuit length.

Example 2 — Commercial Three-Phase Feeder

Scenario: 100A load on #1/0 AWG copper, 200-foot run, 208V three-phase.

VD = (1.732 × 12.9 × 100 × 200) / 105,600

VD = 446,976 / 105,600 = 4.23 volts

Percentage: 4.23 / 208 = 2.03% — Under the 3% recommendation. This wire size works.

Step 4: Check Against NEC Recommendations

The NEC recommends no more than 3% voltage drop on the branch circuit and no more than 5% total (feeder + branch circuit combined). These aren't hard code requirements — they're informational notes — but most inspectors and engineers treat them as the standard.

Common Mistakes

When to Upsize Conductors

If your calculation shows excessive voltage drop, you have two options: upsize the conductor (use a larger wire gauge with more circular mils) or shorten the run (relocate the panel or sub-panel closer to the load). In practice, upsizing the conductor is usually the more practical solution.

On long commercial runs, it's common to go up one or two wire sizes specifically for voltage drop — even when the ampacity of the smaller conductor would be sufficient for the load.

CALCULATE VOLTAGE DROP IN SECONDS

The Master Electrician App has a built-in voltage drop calculator with fractional precision. Just enter your values and get the answer instantly.

⚡ Download Free