The load calculation decides the service size, and the service size decides whether the homeowner can add a heat pump and an EV charger in five years without calling somebody back to tear out the meter base. It is worth doing properly.

Article 220 gives you two legal routes for a dwelling unit: the standard method in Part III, which itemizes every load and applies individual demand factors, and the optional method in Part IV, which applies one simpler set of demand percentages to the whole connected load. Both are valid. This guide walks the standard method, because if you understand it the optional method is twenty minutes of reading.

Note on article numbers. Article 220 was reorganized in the 2023 edition and again in 2026. The requirements are largely consistent but the section numbers moved. This guide describes the requirements rather than reciting numbers, so it holds up across editions. Confirm the numbering against your adopted edition.

Step 1: General lighting load

Multiply the habitable square footage by the general lighting volt-amperes per square foot given for dwelling units, which has long been 3 VA per square foot.

Flow diagram of the standard dwelling unit load calculation showing general lighting load, small appliance and laundry circuits, demand factors, fixed appliances, and the larger of heating or air conditioning
The standard method in order. Skipping a step is how services get undersized.

Use outside dimensions. Include finished, habitable space. Exclude open porches, garages, and unfinished spaces that are not adaptable for future use. An unfinished basement with a stair and a rough opening usually counts, because it is adaptable. A crawl space does not.

General lighting VA = area (sq ft) × 3
Dwelling unit general lighting and general-use receptacles

This single number covers all general lighting and all general-use receptacle outlets. You do not count receptacles separately in a dwelling. That surprises people coming from commercial work.

Step 2: Small appliance and laundry circuits

Add a fixed allowance for each required branch circuit:

  • Small appliance branch circuits: 1500 VA each. A minimum of two are required in any dwelling with a kitchen. If the plans show three, count three.
  • Laundry branch circuit: 1500 VA. One is required where laundry facilities exist or are anticipated.
RUN IT ON THE TAILGATE

The app walks the same sequence and keeps the demand factors straight for you.

These are minimums built into the code, not measured loads. You count them whether or not anybody ever plugs anything in.

Step 3: Apply the demand factor

Add the general lighting load and the small appliance and laundry allowances together, then apply the dwelling unit demand factors to that combined subtotal:

Portion of loadDemand factor
First 3,000 VA100%
From 3,001 to 120,000 VA35%
Remainder over 120,000 VA25%

The logic is that nobody turns on every light and every receptacle in the house at once. The code is willing to bet on that, and it has been right for about eighty years.

The demand factor applies only to this subtotal. Fixed appliances, ranges, dryers, heating and cooling all come in afterward at their own values. Applying the 35 percent to everything is the single most common error on this calculation and it produces a badly undersized service.

Step 4: Fixed appliances

Add the nameplate rating of each appliance fastened in place: water heater, dishwasher, disposal, compactor, attic fan, and similar. Where four or more such appliances are present, a demand factor of 75 percent may be applied to that group. Fewer than four, count them at 100 percent.

Ranges, dryers, and space heating and cooling equipment are excluded from this group. They have their own steps.

Step 5: Range and dryer

Household cooking equipment and electric clothes dryers do not get counted at nameplate. Each has its own demand table.

For a single household range, the demand table lets you count substantially less than the nameplate rating, because a range never runs every element at maximum simultaneously for long. An electric dryer has a minimum counted value with demand factors that apply when several dryers are present.

These tables are short and worth reading directly rather than memorizing. The important thing is knowing that you do not use nameplate here.

Step 6: Heating or cooling, whichever is larger

Space heating and air conditioning are noncoincident loads. They do not run at the same time, so you include the larger and omit the smaller entirely.

One important exception: where a heat pump runs together with supplementary electric resistance heat, both operate simultaneously and both are counted.

Motor loads in this category, like the compressor, are counted with the usual motor considerations, including the requirement to add 25 percent of the largest motor in the calculation.

Step 7: Convert and select

Amperes = total VA ÷ 240
For a standard 120/240 volt single-phase dwelling service

Take the resulting amperes to the next standard overcurrent device rating, then size the service conductors to match, checking termination temperature ratings and the service conductor allowances. See the ampacity guide for that part and breaker sizing for the overcurrent side.

Worked example

A 2,400 square foot house

Three small appliance circuits, one laundry circuit. Water heater 4,500 VA, dishwasher 1,200 VA, disposal 900 VA, attic fan 600 VA. Electric range 12,000 VA nameplate. Electric dryer 5,000 VA. Air conditioning 6,500 VA. Electric heat 10,000 VA.

General lighting: 2,400 × 3 = 7,200 VA
Small appliance: 3 × 1,500 = 4,500 VA
Laundry: 1,500 VA
Subtotal: 13,200 VA

Demand applied:
First 3,000 at 100% = 3,000
Remaining 10,200 at 35% = 3,570
Demand subtotal = 6,570 VA

Fixed appliances (four present, so 75% permitted):
4,500 + 1,200 + 900 + 600 = 7,200 × 0.75 = 5,400 VA

Range at its demand value: 8,000 VA
Dryer: 5,000 VA

Heating vs cooling: heat at 10,000 exceeds A/C at 6,500, so count 10,000 VA and drop the air conditioning.

Total: 6,570 + 5,400 + 8,000 + 5,000 + 10,000 = 34,970 VA

Amperes: 34,970 ÷ 240 = 145.7 amps

Service: a 150 amp service satisfies the calculation. Most contractors would install 200 amps here anyway, and in a moment you will see why.

Why the answer keeps getting bigger

That house calculated at 146 amps. Now add what a homeowner is likely to ask for in the next five years:

  • A 48 amp EV charger. Continuous load, counted at 125 percent, which is 60 amps of calculated capacity at 240 volts, or 14,400 VA.
  • An induction range replacing the existing one, usually a larger nameplate.
  • A heat pump water heater or a second EV.

Add the EV charger alone and the calculation lands near 206 amps. The 150 amp service that was perfectly legal is now a service upgrade, a meter base, a utility coordination and a permit.

This is why load calculations are worth running for the future and not just for the permit. See EV charger circuit sizing for the load management options that can avoid a service upgrade entirely.

Standard versus optional: which to use

Standard methodOptional method
EffortHigher, itemizedLower, one formula
Typical resultLarger numberSmaller number
Best forUnusual loads, additions, disputesStraightforward new dwellings
RestrictionAlways availableConditions apply, including service size

If the optional method gets you under the service size you want and the dwelling meets its conditions, use it. If the numbers are close or the loads are unusual, run the standard method, because that is the one that survives an argument.

Common errors

  • Applying the 35 percent demand factor to appliances and heating instead of only to the lighting subtotal.
  • Counting range and dryer at nameplate instead of using their demand tables.
  • Counting both heating and cooling.
  • Forgetting the 25 percent addition for the largest motor.
  • Including garage and porch area in the square footage.
  • Counting only two small appliance circuits when the plan shows more.
LOAD CALCS WITHOUT THE LEGAL PAD

Step through Article 220 in the app and get your service size. Free tier, works offline.

// Free Download

GET THE FIELD PACK

Two printables: the 22-point rough-in checklist, and branded panel schedules in 24, 30 and 42 circuit that print at 4 by 5 inches and slide straight into a panel sleeve. Enter your email and the downloads open right away.

Your address comes straight to Jason. No list rental, no spam, unsubscribe any time.

Frequently asked questions

What is the difference between the standard and optional load calculation?
The standard method in Article 220 Part III itemizes loads and applies individual demand factors. The optional method in Part IV uses a simpler formula with a single set of demand percentages applied to the whole connected load. Both are legal for dwellings that meet the conditions. The optional method usually produces a smaller number and is what most people use for a straightforward house.
What size service does a typical house need?
The calculation tells you, not a rule of thumb. That said, 200 amp services are the common outcome for modern homes, and the addition of EV charging, heat pumps and induction ranges is pushing more calculations past that. Run the numbers before you promise a panel size.
Do I include both heating and air conditioning?
Only the larger of the two, because they do not run at the same time. The exception is a heat pump with supplemental electric heat that can energize together, in which case both are included.
How does an EV charger change the calculation?
It is a continuous load, so it is calculated at 125 percent of its rating, and it is frequently the load that pushes an existing service over. Load management systems are an accepted way to avoid a service upgrade in some cases. See EV charger circuit sizing.

Keep reading

Calculators

Breaker and Overcurrent Device Sizing: Circuits, Feeders and Motors

Read it →
Field Tips

EV Charger Circuit Sizing: What Article 625 Requires

Read it →
Calculators

Wire Size Chart: Conductor Ampacity Under NEC 310.16

Read it →
NEC Updates

2026 NEC Code Changes: Everything Electricians Need to Know

Read it →
// DisclaimerThe National Electrical Code® (NEC®) and NFPA 70® are registered trademarks and copyrighted publications of the National Fire Protection Association (NFPA). This article is an independent educational resource and is not affiliated with, endorsed by, or sponsored by the NFPA. All code references in this article are paraphrased for educational purposes only and do not reproduce the official text of any NEC edition. This content is not a substitute for the official NFPA 70 publication. Electricians, contractors, and students are encouraged to purchase the official National Electrical Code from the NFPA at nfpa.org for complete and authoritative code text. Always verify requirements with the code edition adopted by your jurisdiction and your Authority Having Jurisdiction (AHJ).