Charts are for the tailgate. When you need to know roughly whether a run is going to be a problem before you order wire, a table beats a formula. When you need to commit to a conductor size, go back and run the calculation.

Read this before you use any of the tables

Every voltage drop chart bakes in assumptions, and most charts online do not tell you what theirs are. Here are ours, stated plainly:

Line chart showing how voltage drop percentage increases with run length for several conductor sizes at a fixed load, with a marked three percent threshold
Each conductor size crosses the 3 percent line at a different distance. That crossing point is what the chart gives you.
  • Copper conductors, using a K value of 12.9 ohm circular mils per foot. For aluminum, multiply every length in these tables by roughly 0.61.
  • 3 percent target, which is the commonly used branch circuit design figure from the code's informational notes. It is a recommendation, not an enforceable limit, unless your specification or AHJ makes it one.
  • One-way distance in feet, from source to load. The formula's factor already accounts for the return path.
  • Unity power factor and normal operating temperature. Motor loads with poor power factor will fall short of these numbers.
  • Circular mil areas from the code's conductor properties table.

These are maximum lengths for a continuously drawn current at the value shown. A circuit that is rarely loaded to its breaker rating will perform better than the table suggests. A circuit that runs at full load all day will not.

120 volt single-phase, 3 percent

ConductorAt 10 AAt 12 AAt 15 AAt 20 A
14 AWG57 ft48 ft38 ft
12 AWG91 ft76 ft61 ft46 ft
10 AWG145 ft121 ft97 ft72 ft
8 AWG230 ft192 ft154 ft115 ft
CHARTS ARE APPROXIMATIONS

For the actual run, the app calculates from your real length, load and conductor.

This is the table that surprises people. A fully loaded 15 amp circuit on 14 AWG crosses 3 percent at 38 feet. Not 38 feet of wall, 38 feet of conductor from the panel. In a two-story house that is a bedroom on the far corner.

240 volt single-phase, 3 percent

ConductorTypical loadMax one-way length
12 AWG20 A91 ft
10 AWG30 A97 ft
8 AWG40 A115 ft
6 AWG50 A146 ft
6 AWG55 A133 ft
4 AWG70 A166 ft
3 AWG85 A173 ft
2 AWG95 A195 ft
1/0125 A236 ft
2/0145 A256 ft
3/0165 A284 ft
4/0195 A303 ft

Doubling the voltage doubles the allowable distance for the same conductor and current, which is why 240 volt circuits reach so much farther than 120 volt circuits.

208 volt three-phase, 3 percent

ConductorLoadMax one-way length
10 AWG30 A97 ft
8 AWG40 A115 ft
6 AWG55 A133 ft
4 AWG70 A167 ft
2 AWG95 A195 ft
1/0125 A236 ft
4/0195 A303 ft

480 volt three-phase, 3 percent

ConductorLoadMax one-way length
8 AWG40 A266 ft
6 AWG55 A307 ft
4 AWG70 A384 ft
2 AWG95 A450 ft
1/0125 A544 ft
4/0195 A699 ft

This is the case for distributing at 480 and stepping down locally rather than running 208 across a large site. Same conductor, same current, more than double the reach. See transformer sizing for the step-down side of that decision.

Adjusting the tables

If you wantDo this to the table length
Aluminum instead of copperMultiply by 0.61
A 5 percent target instead of 3Multiply by 1.67
A 2 percent targetMultiply by 0.67
Half the load shownMultiply by 2
Double the load shownMultiply by 0.5

Length, load and target percentage all scale linearly, which is why these adjustments are simple multiplication. Conductor size does not scale linearly, because circular mils do not double with each AWG step.

What each conductor step buys you

Going up one size increases circular mils by roughly 26 percent, so it buys roughly 26 percent more distance. Going up two sizes buys about 59 percent. That is worth knowing when you are deciding between upsizing and finding a shorter route.

FromToDistance gain
14 AWG12 AWG+59%
12 AWG10 AWG+59%
10 AWG8 AWG+59%
8 AWG6 AWG+59%
6 AWG4 AWG+59%
4 AWG2 AWG+59%

The AWG system is logarithmic, so every two-gauge step is about a 59 percent increase in area. That consistency makes it easy to estimate in your head: two sizes up buys roughly half again the distance.

Where voltage drop actually bites

  • Detached garages and outbuildings. The single most common place a residential circuit fails on drop rather than ampacity.
  • Well pumps. Long runs, motor load, and a motor that runs hot when it is starved for voltage.
  • Site and parking lot lighting. Hundreds of feet is normal, and dim fixtures at the end of the run are a visible callback.
  • Long homeruns in commercial buildings. Panel in a back corner, load at the far end of the floor plate.
  • EV chargers in detached garages. A 60 amp continuous load at 130 feet is not a small drop. See EV charger sizing.

Rule of thumb for triage: if the one-way run is under 100 feet on a 240 volt circuit, or under 50 feet on a 120 volt circuit, you are probably fine and can move on. Anything longer than that, run the numbers.

Remember what this does not answer

Voltage drop and ampacity are separate checks. A conductor that passes this chart can still be undersized for the current it carries, and a conductor that carries the current fine can still drop too much. Size for ampacity using the 310.16 tables and correction factors, then check drop, then install the larger of the two answers.

EXACT NUMBERS, NOT ROUNDED ONES

Enter your actual conditions and get the real drop. Free tier, works offline.

// Free Download

GET THE FIELD PACK

Two printables: the 22-point rough-in checklist, and branded panel schedules in 24, 30 and 42 circuit that print at 4 by 5 inches and slide straight into a panel sleeve. Enter your email and the downloads open right away.

Your address comes straight to Jason. No list rental, no spam, unsubscribe any time.

Frequently asked questions

How far can I run 12 AWG wire?
It depends entirely on the load, the voltage and the target percentage. A lightly loaded 120-volt circuit runs much farther than a fully loaded one before crossing 3 percent. Use a chart to get in the neighborhood and a calculation to commit.
Are voltage drop charts accurate?
They are accurate for the assumptions printed with them, and misleading without those assumptions. Any chart bakes in a conductor material, a temperature, a power factor and a target percentage. Change one and the numbers move.
Does voltage drop matter on short runs?
Rarely on branch circuits inside a typical house. It becomes the controlling factor on long homeruns, detached structures, well pumps, site lighting and anything fed across a parking lot. If the run is over roughly a hundred feet, check it.
How do I fix excessive voltage drop?
Increase the conductor size, shorten the run, raise the system voltage, or reduce the load. Upsizing the conductor is usually the only one available to you. See the step-by-step calculation for how much a size change buys you.

Keep reading

Calculators

How to Calculate Voltage Drop — Step by Step

Read it →
Calculators

Wire Size Chart: Conductor Ampacity Under NEC 310.16

Read it →
Calculators

Breaker and Overcurrent Device Sizing: Circuits, Feeders and Motors

Read it →
Calculators

Residential Load Calculation: Article 220, Step by Step

Read it →
// DisclaimerThe National Electrical Code® (NEC®) and NFPA 70® are registered trademarks and copyrighted publications of the National Fire Protection Association (NFPA). This article is an independent educational resource and is not affiliated with, endorsed by, or sponsored by the NFPA. All code references in this article are paraphrased for educational purposes only and do not reproduce the official text of any NEC edition. This content is not a substitute for the official NFPA 70 publication. Electricians, contractors, and students are encouraged to purchase the official National Electrical Code from the NFPA at nfpa.org for complete and authoritative code text. Always verify requirements with the code edition adopted by your jurisdiction and your Authority Having Jurisdiction (AHJ).